I have messed around with NUT to trigger a graceful shutdown of my home server running Ubuntu Server. I have struggled with setting NUT up on bare metal, but would like a gui anyway. I saw PVE-UPS which looks good, but I think but I think it is meant for Proxmox. Any alternatives, or a spin of PVE-UPS for docker compose anybody know about?

  • mbirth 🇬🇧@lemmy.ml
    link
    fedilink
    English
    arrow-up
    9
    ·
    19 hours ago

    What was the difficulty with NUT for you? The setup is pretty straightforward, IMHO.

    Should be easy to wrap in a container, too.

    • stoicmaverick@lemmy.worldOP
      link
      fedilink
      English
      arrow-up
      1
      ·
      18 hours ago

      I was hoping to setup a server and clients to shutdown the other Raspberry Pis and such, scattered around the house if the main server senses a power failure.

      Also, I had an issue where it insisted on triggering a shutdown the SECOND the UPS triggered, even if it came right back. I might take another swing at it at some point, but I liked the look of that PVE-UPS things.

      • tychosmoose@lemmy.world
        link
        fedilink
        English
        arrow-up
        1
        ·
        12 hours ago

        A basic NUT configuration does an immediate shutdown as soon as an ONBATT status is reached (upssched.conf has “at ONBATT execute…”, which causes the upssched-cmd to run the shutdown command immediately). But you can change that to a timer, which can be cancelled if the UPS goes back online, or only shutdown at LOWBATT.

        It’s complicated, but NUT should be able to do everything you have stated as a goal. But it takes some testing.

        One thing I found helpful while setting it up is the Dummy UPS driver that is included in the documentation. Rather than plug and unplug a physical UPS during testing you can make text files with various ups statuses and cp one to the dummy’s input file target to make it change to battery power or back online. Use logger to log information into the system journal from upssched-cmd to see what’s running in your script (with a unique keyword to grep on). Monitor in another terminal with journalctl -f | grep yourkeyword to view your messages. This made it much easier to get the upssched stuff sorted out.

        One of my goals was unattended power-on management for when I was away from home. If power returned for an amount of time, send power commands to various smart outlets to bring everything back up in sequence. So I used a pretty big upssched-cmd, with timers for both shutdown and power up and different UPS battery levels (no power up until 30% battery, for example). It would have been pretty difficult to debug without the dummy UPS.

        Anyway, NUT is really powerful.

        • stoicmaverick@lemmy.worldOP
          link
          fedilink
          English
          arrow-up
          1
          ·
          12 hours ago

          Thanks. Good info. Feel like sharing your conf file to see how it’s formatted in an example that actually works? Might make this my weeks evening project.

          • tychosmoose@lemmy.world
            link
            fedilink
            English
            arrow-up
            4
            ·
            11 hours ago

            It’s a lot. But here are my most recent notes.

            Note that the pipe & lock locations different by distro, as does the nut username. So these files won’t drop in and work anywhere.

            The dummy driver will need to be installed and configured.

            Mine also have several layers of timers on battery an online:

            1. NUT server: In ONBATT I use sleep commands to time subsequent commands. These will always run.
            2. NUT server: Onbatt5 is a upssched timer I set to 300s and is cancelled if the UPS returns to line power.
            3. NUT client: Onbatt30s starts on the client when it gets an ONBATT status from the server.

            Most configs would have the client side cancel their timers if power returns. In my case I don’t want that because I prefer more certainty of state so that I know it’s safe to power cycle an outlet to bring a device back up. My NUT server runs on an old pi 3b with a read-only file system. So it never needs a safe shutdown. It’s the last man standing to bring everything else back up if the UPS returns to line power before the battery is exhausted. That’s why there is no local shutdown on the NUT server config.

            Each snmpset... is a truncated version of an outlet power command.

            Also, the wall commands were a debug aid. Uncomment to use, but test a command first. Wall doesn’t work on some distros.

            NUT Server

            NUT.CONF:

            	MODE=netserver
            

            UPS.CONF:

            	[ups]
            	desc = My UPS
            	driver = dummy-ups
            	port = /opt/ups/ups.seq
            

            UPSD.CONF:

            	LISTEN 0.0.0.0 3493
            	## all interfaces
            	## STATEPATH /var/run/nut
            

            UPSD.USERS:

            	[upsuser]
            	  password = <pw>
            	  actions = set
            	  upsmon master
            	[upssrv]
            	  password = <pw>
            	  actions = set
            	  upsmon slave
            	[upspi]
            	  password = <pw>
            	  actions = set
            	  upsmon slave
            

            UPSMON.CONF:

            	RUN_AS_USER nut
            	#RUN_AS_USER root
            	MONITOR ups@localhost 1 upsuser <pw> master
            	NOTIFYMSG ONLINE "UPS %s on line power"
            	NOTIFYMSG ONBATT "UPS %s on battery"
            	NOTIFYMSG LOWBATT "UPS %s battery is low"
            	NOTIFYMSG FSD "UPS %s: forced shutdown in progress"
            	NOTIFYMSG COMMOK "Communications with UPS %s established"
            	NOTIFYMSG COMMBAD "Communications with UPS %s lost"
            	NOTIFYMSG SHUTDOWN "Auto logout and shutdown proceeding"
            	NOTIFYMSG REPLBATT "UPS %s battery needs to be replaced"
            	NOTIFYMSG NOCOMM "UPS %s is unavailable"
            	NOTIFYMSG NOPARENT "upsmon parent process died - shutdown impossible"
            	
            	NOTIFYFLAG ONLINE WALL+EXEC+SYSLOG
            	NOTIFYFLAG ONBATT WALL+EXEC+SYSLOG
            	NOTIFYFLAG LOWBATT SYSLOG+WALL
            	NOTIFYFLAG FSD SYSLOG+WALL
            	NOTIFYFLAG COMMOK SYSLOG+WALL
            	NOTIFYFLAG COMMBAD SYSLOG+WALL
            	NOTIFYFLAG SHUTDOWN SYSLOG+WALL
            	NOTIFYFLAG REPLBATT SYSLOG+WALL
            	NOTIFYFLAG NOCOMM SYSLOG+WALL
            	NOTIFYFLAG NOPARENT SYSLOG+WALL
            	
            	MINSUPPLIES 1
            	SHUTDOWNCMD "/sbin/shutdown -P +0"
            	NOTIFYCMD "/usr/sbin/upssched"
            	POLLFREQ 5
            	POLLFREQALERT 5
            	HOSTSYNC 15
            	DEADTIME 15
            	# POWERDOWNFLAG /var/run/killpower
            	RBWARNTIME 43200
            	NOCOMMWARNTIME 300
            	FINALDELAY 5
            	CERTVERIFY 0
            	FORCESSL 0
            	
            	UPSSCHED.CONF:
            	CMDSCRIPT /etc/nut/upssched-cmd
            	PIPEFN /var/run/nut/upssched.pipe
            	LOCKFN /var/run/nut/upssched.lock
            	
            	AT ONBATT ups@localhost CANCEL-TIMER online3
            	AT ONBATT ups@localhost CANCEL-TIMER online10
            	AT ONBATT ups@localhost START-TIMER onbatt5 300
            	AT ONBATT ups@localhost EXECUTE onbattnotify
            	
            	AT ONLINE ups@localhost CANCEL-TIMER onbatt5
            	AT ONLINE ups@localhost START-TIMER online3 180
            	AT ONLINE ups@localhost START-TIMER online10 600
            	AT ONLINE ups@localhost EXECUTE onlinenotify
            

            UPSSCHED-CMD

            	#! /bin/bash
            	#
            	# This script should be called by upssched via the CMDSCRIPT directive
            	# The first argument passed to your CMDSCRIPT is the name of the timer
            	# from your AT lines.
            	logger -t upssched-cmd "Calling upssched-cmd $1"
            	wall "Calling upssched-cmd $1"
            	UPS="ups@localhost"
            	HOST=$( uname -n)
            	TIMESTAMP=$(date +%Y%m%d%H%M%S)
            	STATUS=$( upsc $UPS ups.status )
            	CHARGE=$( upsc $UPS battery.charge )
            	CHMSG="UPS[STATUS]:$CHARGE%"
            	case $1 in
            			onbattnotify)
            					# srv and pi are upsmon clients and will shut down on their own after a 30s delay.
            					# Log the Notification.
            					logger -t upssched-cmd "UPS on Battery Power. Servers will shutdown in 30 seconds. Switch shutdown in 5 minutes. $CHMSG $TIMESTAMP"
            					wall "upssched-cmd onbattnotify: UPS on Battery Power. Servers will shutdown in 30 seconds. Switch shutdown in 5 minutes. $CHMSG"
            	#                wall "upssched-cmd: sleeping to give servers time to poweroff"
            					sleep 120s
            					# Power off PDU outlets to save power.
            					logger -t upssched-cmd "UPS on Battery Power. PDU outlets 4-srv-drives, 5-srv, 7-pi and 8-homeassistant power down NOW. $CHMSG $TIMESTAMP"
            					snmpset ...
            					snmpset ...
            					snmpset ...
            					snmpset ...
            	#                wall "End upssched-cmd $1"
            					;;
            			onbatt5)
            					# Shut down servers
            					logger -t upssched-cmd "UPS on Battery Power. PDU outlets 3-switch and 8-homeassistant power down NOW. $CHMSG $TIMESTAMP"
            					snmpset ...
            					snmpset ...
            	#                wall "End upssched-cmd $1"
            					;;
            			onlinenotify)
            					# Log the notification.
            					logger -t upssched-cmd "UPS back on Line Power. Bringing up network in 3 minutes, servers in 10 minutes. $CHMSG $TIMESTAMP"
            	#                wall "End upssched-cmd $1"
            					;;
            			online3)
            					# Power on PDU outlets for main switch to prep for server startup.
            					logger -t upssched-cmd "UPS back on Line Power. Bringing up PDU outlet 3-switch NOW. $CHMSG $TIMESTAMP"
            					snmpset ...
            	#                wall "End upssched-cmd $1"
            					;;
            			online10)
            					# Power on PDU outlets for servers now.
            					logger -t upssched-cmd "UPS on Line Power. Bringing up PDU outlets 5-srv, 7-pi, 8-homeassistant NOW. $CHMSG $TIMESTAMP"
            					snmpset ...
            					snmpset ...
            					snmpset ...
            	#                wall "End upssched-cmd $1"
            					;;
            			upsgone)
            					logger -t upssched-cmd "UPS communication has been gone awhile on $HOST. $TIMESTAMP"
            					;;
            			)
            					logger -t upssched-cmd "Unrecognized command: $1"
            					;;
            	esac
            

            NUT Client

            NUT.CONF

            MODE=netclient
            

            UPS.CONF

            maxretry = 3
            

            UPSD.CONF

            # empty
            

            UPSD.USERS

            # empty
            

            UPSMON.CONF

            RUN_AS_USER nut  
              
            MONITOR ups@192.168.0.77 1 upspi <pw> slave  
            NOTIFYCMD /usr/sbin/upssched  
            SHUTDOWNCMD "sudo /sbin/shutdown -P +0"  
              
            NOTIFYMSG ONLINE "UPS %s on line power"  
            NOTIFYMSG ONBATT "UPS %s on battery"  
            NOTIFYMSG LOWBATT "UPS %s battery is low"  
            NOTIFYMSG FSD "UPS %s: forced shutdown in progress"  
            NOTIFYMSG COMMOK "Communications with UPS %s established"  
            NOTIFYMSG COMMBAD "Communications with UPS %s lost"  
            NOTIFYMSG SHUTDOWN "Auto logout and shutdown proceeding"  
            NOTIFYMSG REPLBATT "UPS %s battery needs to be replaced"  
            NOTIFYMSG NOCOMM "UPS %s is unavailable"  
            NOTIFYMSG NOPARENT "upsmon parent process died - shutdown impossible"  
              
            NOTIFYFLAG ONLINE WALL+EXEC+SYSLOG  
            #+SYSLOG+WALL  
            NOTIFYFLAG ONBATT WALL+EXEC+SYSLOG  
            #+SYSLOG+WALL  
            NOTIFYFLAG LOWBATT SYSLOG+WALL  
            NOTIFYFLAG FSD SYSLOG+WALL  
            NOTIFYFLAG COMMOK SYSLOG+WALL  
            NOTIFYFLAG COMMBAD SYSLOG+WALL  
            NOTIFYFLAG SHUTDOWN SYSLOG+WALL  
            NOTIFYFLAG REPLBATT SYSLOG+WALL  
            NOTIFYFLAG NOCOMM SYSLOG+WALL  
            NOTIFYFLAG NOPARENT SYSLOG+WALL  
            
            MINSUPPLIES 1  
            POLLFREQ 10  
            POLLFREQALERT 5  
            HOSTSYNC 15  
            DEADTIME 15  
            RBWARNTIME 43200  
            NOCOMMWARNTIME 300  
            FINALDELAY 5
            

            UPSSCHED.CONF

            CMDSCRIPT /etc/nut/upssched-cmd  
            PIPEFN /run/nut/upssched.pipe  
            LOCKFN /run/nut/upssched.lock  
              
            AT ONBATT ups@192.168.0.77 EXECUTE onbattnotify  
            AT ONBATT ups@192.168.0.77 START-TIMER onbatt30s 30
            
            # Disabled the online cancel actions in favor of having certainty on the state.
            # Servers will go down on an OB event, but that's fine. When Nutpi sees it back
            # OL it will bring up the servers
            #AT ONLINE ups@192.168.0.77 CANCEL-TIMER onbatt30s  
            #AT ONLINE ups@192.168.0.77 EXECUTE onlinenotify
            

            UPSSCHED-CMD

            #! /bin/sh  
            #  
            # This script should be called by upssched via the CMDSCRIPT directive.  
            #  
            # The first argument passed to your CMDSCRIPT is the name of the timer  
            # from your AT lines.  
              
            logger -i -t upssched-cmd "Calling upssched-cmd $1"  
            UPS="ups@192.168.0.77"  
            HOST=$( uname -n)  
            STATUS=$( upsc $UPS ups.status 2>&1 | grep -v '^Init SSL' )  
            CHARGE=$( upsc $UPS battery.charge 2>&1 | grep -v '^Init SSL' )  
            CHMSG="$UPS[$STATUS]:$CHARGE%"  
              
            case $1 in  
            onbattnotify)  
            # Log the Notification.  
            logger -t upssched-cmd "UPS on Battery Power. Shutting down $HOST in 30 seconds. $CHMSG"  
            wall "upssched-cmd: UPS on Battery Power. Shutting down $HOST in 30 seconds. $CHMSG"  
            ;;  
            onbatt30s)  
            # Shut down servers  
            logger -t upssched-cmd "UPS on Battery Power. $HOST shutting down NOW. $CHMSG"  
            wall "upssched-cmd: UPS on Battery Power. $HOST shutting down NOW. $CHMSG"  
            sudo shutdown -P +0  
            ;;  
            # onlinenotify)  
            # # Log the notification.  
            # logger -t upssched-cmd "UPS back on Line Power. $HOST is already online. $CHMSG"  
            # wall "upssched-cmd: UPS back on Line Power. $HOST is already online. $CHMSG"  
            # ;;  
            upsgone)  
            logger -t upssched-cmd "UPS communication has been gone awhile on $HOST."  
            ;;  
            *)  
            logger -t upssched-cmd "Unrecognized command: $1"  
            ;;  
              
            esac
            
      • mbirth 🇬🇧@lemmy.ml
        link
        fedilink
        English
        arrow-up
        2
        ·
        17 hours ago

        On clients you mostly have to set MODE=netclient in the nut.conf and modify the upsmon.conf according to the manual and detailed manual. By default, it should only shutdown systems when reaching a “low battery” situation, not immediately when switching to battery power.

  • neidu4@piefed.social
    link
    fedilink
    English
    arrow-up
    4
    ·
    16 hours ago

    Note to self: Get around to wiring my UPS onto my management network for monitoring and graceful shutdown of non-essential stuff.

    • Ajen@sh.itjust.works
      link
      fedilink
      English
      arrow-up
      3
      ·
      16 hours ago

      It’s also a good idea to gracefully shutdown anything essential that isn’t using a read-only rootfs. I’ve got my NAS configured to shut down after 5 minutes, but my firewall and frigate server keep running until the battery is almost dead, then safely shut down if the power still hasn’t come back yet.